Remove and Install the IP54/IP21, 400/800 mm Wide Door Vent Exhaust Fan and Filter Assembly for Frames 8...15
Replace the IP54/IP21, 400 mm or 800 mm wide door vent exhaust fan and filter assembly with the appropriate kit catalog number:
- 400 mm wide entry/exit bay SK-RM-WBDR-FANFLR1
- 800 mm wide entry/exit bay SK-RM-WBDR-FANFLR2
Follow these steps to remove and install the IP54/IP21, 400 mm or 800 mm wide door vent exhaust fan and filter assembly.
- Review the product advisories in Before You Begin.
- Remove power from the system.
- Open the wire bay enclosure door.
- On the inside of the enclosure door, remove the M8 hex nut and washer that secures the two ground wire lugs to the door, and remove the wires.
- Disconnect the fan power wires from connector P1 (A) on the fan assembly.
- Press the tabs on the vent cover inward and pull the vent off the front of the enclosure door.
- Install the IP54/IP21, 400/800 mm wide door vent exhaust fan, and filter assembly in the reverse order of removal.