Remove and Install the Power Module PE-B1 Power Jumper for Frames 8...15

Replace the power module PE-B1 power jumper with kit catalog number SK-RM-INV-JMPR-F8. Follow these steps to remove and install the power module PE-B1 power jumper.
  1. Review the product advisories in Before You Begin.
  2. Remove power from the system.
  3. Open the corresponding enclosure door.
  4. If present, remove the guards from the enclosure.
  5. Loosen the thumb screw that secures the connections cover to the front of the power module.
  6. Use the screw to lift the connections cover up and off the power module chassis.
  7. Remove the jumper from connector P5 or P6 on the power layer interface circuit board.
    example of how to remove the connections cover and the PE-B1 power jumper from a power module
  8. IMPORTANT: If present, do not remove the protective cover from the unused jumper socket (J5 or J6) on the power interface circuit board.
  9. Install the power module PE-B1 power jumper in the reverse order of removal. Verify that the jumper PE-B1 is installed in the same position on the new power module as it was on the old power module.