Remove and Install the IP21, 400/600 mm Wide Door Vent Filter for Frames 8...15

Replace the IP21, 400/600 mm wide door vent filter with kit catalog number SK-RM-PB4DR-21FLTR1 (400 mm wide enclosure) or SK-RM-PB6DR-21FLTR1 (600 mm wide enclosure). Follow these steps to remove and install the IP21, 400/600 mm wide door vent filter.
  1. Review the product advisories in Before You Begin.
  2. Remove power from the system.
  3. Loosen the two or three slotted-Phillips head, captive screws that secure the filter cassette cover and metal mesh screen to the cassette chassis on the door and remove the cover and metal mesh filter.
  4. Remove the metal mesh filter from the cover.
    example of how to remove the IP21 door vent filter from a 400 mm or 600 mm wide power bay
  5. IMPORTANT: Verify that the weep holes on the metal mesh filter are at the bottom of the filter when installed.
  6. Place the slots on the cassette cover on the tabs on the door vent chassis.
  7. Insert the filter in the cassette chassis on the door and close and secure the cassette cover to the door.