Remove and Install the IP54/IP21, 400/600 mm Wide Door Vent Filters for Frames 8...15
Replace the IP54/IP21, 400/600 mm wide door vent filter with it catalog number SK-RM-IB4DR-FLTR1 (400 mm wide door) or SK-RM-IB6DR-FLTR1 (600 mm wide door). Follow these steps to remove and install the IP54/IP21, 400/600 mm wide door vent filters.
- Review the product advisories in Before You Begin.
- Remove power from the system.
- Lift the tab (A) on the top center of the vent cover and lower the cover.
- Remove the filter media (B) from the vent.
- IMPORTANT: Verify that the Rittal logo on the fiber filter media points inward, toward the interior of the enclosure.
- Install the IP54/IP21, 400/600 mm wide door vent filters in the reverse order of removal.