Remove and Install the IP54/IP21, 1000 mm Wide Door Vent Fan for Frames 8...15

Replace the IP54/IP21, 1000 mm wide door vent fan for an input bay with kit catalog number SK-RM-IBDR-FAN1. Follow these steps to remove and install the IP54/IP21, 1000 mm wide door vent fan.
  1. Review the product advisories in Before You Begin.
  2. Remove power from the system.
  3. Open the input bay enclosure door.
  4. Disconnect the connectors P12 or P13 from the fans on the door.
  5. Remove the four M4 x 14 mm Torx screws that secure the fan to the door and remove the fan.
    example of how to remove the fan from a 1000 mm wide input bay door
  6. IMPORTANT: Verify that the airflow direction arrow on the fan points inward, toward the interior of the enclosure.
  7. Install the door vent fans in the reverse order of removal.