Remove and Install the Input Bay 240V Power Distribution Fuse (FH2) for Frames 8...15

Replace the 240V power distribution fuse (labeled FH2) with the appropriate kit catalog number that is identified in these tables. Each kit contains one fuse.
Frame 8 Fuses
Cat. No.
Voltage Class
Fuse Amp Rating
Enclosure IP Rating
Required Fuse Quantity
SK-RM-IBFH2-FUSE2A-F8
400V/480V/600V
15
IP21
1
SK-RM-IBFH2-FUSE2B-F8
690V
16
IP21
1
SK-RM-IBFH2-FUSE2C-F8
400V/480V/600V
20
IP54
1
SK-RM-IBFH2-FUSE2D-F8
690V
20
IP54
1
Frame 9 Fuses
Cat. No.
Voltage Class
Fuse Amp Rating
Enclosure IP Rating
Required Fuse Quantity
SK-RM-IBFH2-FUSE2E-F9
400V/480V/600V
25
IP21
1
SK-RM-IBFH2-FUSE2F-F9
690V
25
IP21
1
SK-RM-IBFH2-FUSE2G-F9
400V/480V/600V
35
IP54
1
SK-RM-IBFH2-FUSE2H-F9
690V
40
IP54
1
Frame 10 Fuses
Cat. No.
Voltage Class
Fuse Amp Rating
Enclosure IP Rating
Required Fuse Quantity
SK-RM-IBFH2-FUSE2G-F9
400V/480V/600V
35
IP21
1
SK-RM-IBFH2-FUSE2H-F9
690V
40
IP21
1
SK-RM-IBFH2-FUSE2I-F10
400V/480V/600V
60
IP54
1
SK-RM-IBFH2-FUSE2J-F10
690V
63
IP54
1
Frame 11 Fuses
Cat. No.
Voltage Class
Fuse Amp Rating
Enclosure IP Rating
Required Fuse Quantity
SK-RM-IBFH2-FUSE2K-F11
400V/480V/600V
45
IP21
1
SK-RM-IBFH2-FUSE2L-F11
690V
50
IP21
1
SK-RM-IBFH2-FUSE2M-F11
400V/480V/600V
70
IP54
1
SK-RM-IBFH2-FUSE2N-F11
690V
80
IP54
1
Frame 12 Fuses
Cat. No.
Voltage Class
Fuse Amp Rating
Enclosure IP Rating
Required Fuse Quantity
SK-RM-IBFH2-FUSE2I-F10
400V/480V/600V
60
IP21
1
SK-RM-IBFH2-FUSE2J-F10
690V
63
IP21
1
SK-RM-IBFH2-FUSE2O-F12
400V/480V/600V
70
IP54
1
SK-RM-IBFH2-FUSE2P-F12
690V
80
IP54
1
Frame 13 Fuses
Cat. No.
Voltage Class
Fuse Amp Rating
Enclosure IP Rating
Required Fuse Quantity
SK-RM-IBFH2-FUSE2G-F9
400V/480V/600V
35
IP21
2
SK-RM-IBFH2-FUSE2H-F9
690V
40
IP21
2
SK-RM-IBFH2-FUSE2I-F10
400V/480V/600V
60
IP54
2
SK-RM-IBFH2-FUSE2J-F10
690V
63
IP54
2
Frame 14 Fuses
Cat. No.
Voltage Class
Fuse Amp Rating
Enclosure IP Rating
Required Fuse Quantity
SK-RM-IBFH2-FUSE2K-F11
400V/480V/600V
45
IP21
2
SK-RM-IBFH2-FUSE2L-F11
690V
50
IP21
2
SK-RM-IBFH2-FUSE2M-F11
400V/480V/600V
70
IP54
2
SK-RM-IBFH2-FUSE2N-F11
690V
80
IP54
2
Frame 15 Fuses
Cat. No.
Voltage Class
Fuse Amp Rating
Enclosure IP Rating
Required Fuse Quantity
SK-RM-IBFH2-FUSE2I-F10
400V/480V/600V
60
IP21
2
SK-RM-IBFH2-FUSE2J-F10
690V
63
IP21
2
SK-RM-IBFH2-FUSE2O-F12
400V/480V/600V
70
IP54
2
SK-RM-IBFH2-FUSE2P-F12
690V
80
IP54
2
The 240V power distribution fuse holder (labeled FH2) is on the control panel in the input bay. Follow these steps to remove and install the 240V power distribution fuse.
  1. Review the product advisories in Before You Begin.
  2. Remove power from the system.
  3. Open the enclosure door.
  4. Remove the guard from the enclosure.
  5. Pull out on the tab at the top of the fuse holder and remove the fuse.
    example of how to remove the 240V power distribution (FH2) fuse in a frame 8…15 input bay
  6. Item
    Description
    Item
    Description
    A
    Frames 8 and 9 Input Bay
    B
    Frames 8…15 Input Bay (Frame 10 Shown)
  7. Install the 240V power distribution fuse in the reverse order of removal.
Provide Feedback