Remove and Install the IP54, 800/1000 mm Wide Door Vent Filters for Frames 7 and 8...15

Replace the IP54 door vent filters for an 800 mm wide power bay or 1000 mm wide input bay with kit catalog number SK-RM-PB8DR-54FLTR1. Follow these steps to remove and install the IP54, 800/1000 mm wide door vent filters.
  1. Review the product advisories in Before You Begin.
  2. Remove power from the system.
  3. Loosen the four slotted-Phillips head, captive screws that secure the filter cassette cover and metal mesh filter to the cassette chassis on the door.
  4. Remove the metal mesh filter from the cover.
  5. Pull the top edge of the fiber filter out and lift it off the cassette on the door.
    example of how to remove the filters from the 800 mm or 1000 mm wide enclosure door vent assembly
  6. IMPORTANT: Verify that the weep holes on the metal mesh filter are at the bottom of the filter when installed.
  7. Insert the new metal mesh filter into the filter cassette cover.
  8. Place the slots on the cassette cover on the tabs on the door vent chassis.
  9. IMPORTANT: Verify that the airflow direction arrow on the fiber filter media points inward, toward the interior of the enclosure.
  10. Insert the fiber filter in the cassette chassis on the door and close and secure the cassette cover with metal mesh filter to the door.