Remove and Install the Stirring Fan 2 Assembly - Frame 6L

Replace a stirring fan 2 assembly with kit catalog number SK-RM-SFAN2-F6L. Follow these steps to remove and install the stirring fan 2 assembly.
  1. Review the product advisories in Before You Begin.
  2. Remove power from the system.
  3. Remove the cover from the chassis. See Remove and Install the Frame 6L Cover.
  4. Disconnect the fan power wire harness connector P41 from connector J41 on the chassis.
  5. Loosen the two M4 captive, slotted-Torx screws that secure the fan assembly to the chassis and remove the fan assembly.
     example of how to remove the frame 6L liquid cooled drive stirring fan 2 assembly
  6. Install the stirring fan 2 assembly in the reverse order of removal.