Remove and Install the Stirring Fan 1 Assembly - Frame 6L
Replace a stirring fan 1 assembly with kit catalog number SK-RM-SFAN1-F6L. Follow these steps to remove and install the stirring fan 1 assembly.
- Review the product advisories in Before You Begin.
- Remove power from the system.
- IMPORTANT: The fan assembly power wire harness is connected inside the chassis. You cannot remove the fan assembly until you disconnect the fan power wire harness.
- Remove the four M4 x 10 mm slotted-Torx screws that secure the fan assembly to the chassis and pull the fan assembly away from the chassis to expose the fan power wire harness connection.
- Reach into the chassis and disconnect connector P40 from J40 and remove the fan assembly.
- Install the stirring fan 1 assembly in the reverse order of removal.