Test Frame 8...15 Component Fuses

Follow these steps to perform a continuity test on frames 8…15 component fuses.
  1. Review the product advisories in Before You Begin.
  2. Remove power from the system.
  3. Open the enclosure door.
  4. Continuity test these fuses:
    • AC precharge control board fuses (FH1)
    • 240V power distribution fuse (FH2)
    • Input bay 240V control power fuse (FH3)
    • Control transformer fuses (FH4…FH7)
    • AC precharge fused disconnect fuses (FD1)
    • IP54 exhaust fan fuse
    • LCL filter and power module heatsink fan fuse (F1)
  5. Replace all fuses as necessary.
Provide Feedback
Have questions or feedback about this documentation? Please submit your feedback here.