Generic ASCII Receive View
    Use Generic ASCII Receive view to configure parameters for receiving ASCII data through
            serial module.
Generic ASCII Receive View Example

| Parameter | Definition | Available Choices | 
|---|---|---|
| Swap Mode | Determines how the data that is received from the Serial port is
                                    arranged. The swap is performed after the module receives input
                                    data.  | 
 
     TIP: 
    A, B, C, and D represent
                                        four adjacent bytes in the received/transmitted data. | 
| Handshake Mode | Determines how the serial module passes the received data from
                                    the Serial port to the controller. | 
 | 
| Message Timeout | Specifies the receive timeout value (ms). The timer resets every
                                    time that the module receives a new byte from the Serial
                                    port. | 
 | 
| Pad Character | Specifies the character that fills the remaining receive data
                                    buffer when the buffer is not full. | 
 | 
| Start Mode | Determines the usage of the Start Delimiter in the data.  | 
 | 
| Start Delimiter | Defines the character to signal the beginning of the data. All
                                    data received from the Serial port before this value is
                                    disposed. | 
 | 
| Termination Mode | Determines the usage of the Termination Delimiters in the
                                    data. | 
 The end of data received for each record is determined by one of
                                    the following: 
 | 
| Termination Delimiter 1 | Specifies the channel's first Termination Delimiter. The
                                    Termination Delimiter is used to signal the end of the data. | 
 | 
| Termination Delimiter 2 | Specifies the channel's second Termination Delimiter. | 
 If you enter $, it means that the Termination Delimiter 2 is not
                                    used. | 
| XON/XOFF | Enables and disables the flow control of the channel. Select the
                                    checkbox to enable the functionality. When the Serial port receive buffer free space falls to 20%, XOFF
                                    (0x13) character is transmitted. When the Serial port receive
                                    buffer free space reaches 80%, XON (0x11) character is
                                    transmitted.  When XOFF (0x13) character is received, Serial port transmission
                                    is suspended until XON (0x11) is received or a timeout of 60
                                    seconds has elapsed. 
     TIP: 
    XON/XOFF is supported
                                        only in the following combinations: 
 | 
 | 
| Echo Mode | Enables and disable the character echo. Select the checkbox to
                                    cause the module to send immediately all bytes received from the
                                    Serial port back to the device that sent it.  
     TIP: 
    Echo Mode is supported
                                        only in the following combinations: 
 | 
 | 
| Delete Mode | Determines the mode of the Delete character and affects the
                                    characters echoed back to the remote device. | 
 | 
| Read Buffer Size | Specifies the maximum length (in bytes) of the Read Buffer. | 1…256 (default = 256) | 
| Diagnostics | When controller status is online, open the Diagnostics dialog to
                                    view the diagnostic counters for performance and error
                                    management with the Generic ASCII communication. | – | 