De-energize Systems with 755TM Bus Supplies and Common Bus Inverters
This procedure applies to systems without 24V auxiliary power and without separate 240V control power.
Bus supplies ordered with the -C1 control transformer option do not require separate 240V control power.
PowerFlex 755TM System without 24V Auxiliary Power and without 240V Control Power
De-energize the product in the following sequence:
- Turn the control power switches (D) for the common bus inverters to the ‘Off’ position when the drive system is not in operation.
- Turn the DC precharge switches (C) for the common bus inverters to the ‘Off’ position when the drive system is not in operation. This step is not required for common bus inverters without DC precharge.
- Turn the fused disconnect switch (B) to the ‘Off’ position.
- De-energize three-phase power (A). This may not be needed.