5034-OB16 and 5034-OB16XT Digital 16 Output Modules

5034-OB16 and 5034-OB16XT Wiring Diagram
5034-OB16 and 5034-OB16XT Functional Block Diagram
Technical Specifications - 5034-OB16, 5034-OB16XT
Attribute
5034-OB16, 5034-OB16XT
On-state voltage range
10…30V DC
On-state voltage drop, max
0.25V DC
On-state current per point, min
1 mA
Off-state voltage, max
Off-state open wire detection disabled
5V DC with 1 mA min load
Off-state voltage, max
Off-state open wire detection enabled
5V DC with 5 mA min load
Off-state leakage current per point, max
Off-state open wire detection disabled
0.05 mA
Off-state leakage current per point, max
(1)
Off-state open wire detection enabled
0.5 mA
Output current rating per point, max
0.5 A
Output current rating per module, max
5 A
Surge current per point, max
1.5 A for 10 ms, repeatable every 3 s
Fast inductive load turn-off
Yes
Inductive load allowed, max
1.2 H
Output clamping voltage for inductive load when turn off
SA voltage - 44V
Typical is -20V when SA voltage is 24V
Output delay time (backplane to screw), max
Off-to-On
On-to-Off
120 µs @ 0.5 A
Pulse width, min
200 µs
Open load detection diagnostics
Yes, configurable (Default is off)
Output short circuit/overload detection
Yes
Output short circuit/overload protection
Yes
Pilot duty rating
1.5 A inrush current, 0.5 A rated current, DC-14
Output states in program mode per point
Hold Last State
On
Off (Default)
Output states in fault mode per point
Hold Last State
On
Off (Default)
Duration of fault mode per point
1 s
2 s
5 s
10 s
Forever (Default)
Output final state after fault mode per point
On
Off (Default)
Scheduled outputs
Supported, accuracy ±100 µs
(1) Recommended Loading Resistor - To limit the effects of leakage current through solid-state outputs, you can connect a loading resistor in parallel with your load. For 24V DC operation, use a 5.6 kΩ, 0.5 W resistor for transistor operation.
General Specifications - 5034-OB16, 5034-OB16XT
Attribute
5034-OB16, 5034-OB16XT
Number of outputs
16 channels (1 group of 16), sourcing
Voltage category
24V DC source
Output voltage, nom
24V DC
Output voltage range
10…30V DC
SA power voltage, nom
24V DC
SA power voltage range
10…30V DC
SA power current, nom
5.1 A
SA power current, max
5.2 A
SA power current at no load
13 mA
SA reverse polarity protection
Yes
Power dissipation, max
(1)
1.02 W
Thermal dissipation, max
(1)
3.48 BTU/hr
Isolation voltage
250V (continuous), Basic Insulation Type, System to Field
No isolation between SA power and outputs
No isolation between individual outputs
RIUP support
Yes
CIP Sync
Yes, slave only ordinary clock
Electronic keying
Electronic keying via programming software
RTB key positions (slot)
1, 5, 11
RTB supported
5034-RTB18, 5034-RTB18S
Wiring category
(2)
2 - Signal ports
2 - Power ports
Wiring specification
See Wiring Specifications for Removable Terminal Blocks in the PointMax I/O System Specifications Technical Data, publication 5034-TD001
Indicators
1 green/red module status indicator
1 green/red SA power status indicator
16 yellow/red I/O status indicators
Dimensions (HxWxD), approx
123.6 x 15.0 x 66.4 mm (4.87 x 0.59 x 2.61 in.)
Weight, approx
43.0 g (1.52 oz.) – 5034-OB16
45.0 g (1.59 oz.) – 5034-OB16XT
Enclosure type
None (Open-style)
North American temp code
T4
UKEX/ATEX temp code
T4
IECEx temp code
T4
(1) Value is measured at 60 °C (140 °F). Power dissipation varies with temperature.