Point Status Indicators

Interpret Point Status Indicators – Safety I/O Modules
Indicator State
Description
Recommended Action
Off
One of the following:
  • The point is Off.
  • There is no backplane power.
  • The point is not used.
One of the following:
  • Confirm that the point is configured properly.
  • Confirm that there is backplane power supplied through the EtherNet/IP adapter.
Steady yellow
The point is On.
None
Flashing red
The module experienced one or more recoverable faults.
Locate and correct the faults.
Steady red
One of the following:
  • A Field Power Loss condition exists.
  • An internal channel fault exists.
One of the following:
  • Locate and correct the cause of field power loss condition.
  • Locate and correct the internal fault.