Safety Output Module Safety Data

5034-OB8S and 5034-OB8SXT Digital Safety Parameter Data
Attribute
Point Operation Type
Single Channel
Dual Channel
Total Failure Rate (λ (safety related))
4.00535E-06
4.09308E-06
Safe Failure Fraction (SFF)
99.997%
99.997%
Safe Failure Rate (λ
S
)
2.00268E-06
2.04647E-06
Diagnostic Coverage (DC)
99.993%
99.994%
Safe Detected Failure Rate (λ
SD
)
2.00254E-06
2.04635E-06
Safe Undetected Failure Rate (λ
SU
)
1.31748E-10
1.21177E-10
Dangerous Failure Rate (λ
D
)
2.00268E-06
2.04660E-06
Dangerous Detected Failure Rate (λ
DD
)
2.00254E-06
2.04648E-06
Dangerous Undetected Failure Rate (λ
DU
)
1.31748E-10
1.21184E-10
Diagnostic Test Interval (DTI) (hours)
8
8
Hardware Fault Tolerance (HFT)
0
1
Spurious Trip Rate (STR)
3.327E-06
3.835E-06
Mean Time to Failure, Spurious (MTTF-spurious), (hours)
300547
260773
PFH (1/hours)
1.317E-10
1.212E-10
PFD
avg
, at Mission Time of 20 years
4.075E-05
1.062E-05
Safety Reaction Time (SRT), (millisecond)
Condition for Safety Reaction Time is no more than 1 demand per 1.5 seconds.
6
6
Mean Time to Fail Dangerous (MTTF
D
) = 1/λ
D
Mean Time to Repair (MTTR) is 8 Hours = DTI
Provide Feedback
Have questions or feedback about this documentation? Please submit your feedback here.
Normal