Calibration Impacts Data Quality

When a channel on an analog input module is being calibrated, the Notch Filter setting for that channel changes to 10 Hz. The I.Chxx.Uncertain tag is set to 1 for that channel until calibration is completed.
Grouped inputs share an Analog-to-Digital converter. As a result when any input channel is in the calibration process, the
I.Chxx.Uncertain
tag is set to 1 for other input channels in that group. This is because the data sampling rate slows for all input channels in the group.
Provide Feedback
Have questions or feedback about this documentation? Please submit your feedback here.