Diagnostic Assembly
    - Diagnostic Digital Configurable 8 Point with Diagnostics Assembly A- Instance ID = 0x801B (32,795)
- Size = 232 bytes
 Diagnostic Assembly Instance – 32,795NameData TypeSize in BytesRunModeBOOL1InfoBits_Pad1BOOLDiagnosticActiveBOOLCIPSyncValidBOOLCIPSyncTimeoutBOOLInfoBits_Pad5BOOLFieldPowerOffBOOLInfoBits_Pad7BOOLDiagnosticSequenceCountSINT1DiagBits_Pad0BOOL2DiagBits_Pad1BOOLDiagBits_Pad2BOOLDiagBits_Pad3BOOLDiagBits_Pad4BOOLDiagBits_Pad5BOOLDiagBits_Pad6BOOLDiagBits_Pad7BOOLDiagBits_Pad8BOOLDiagBits_Pad9BOOLBaseUnsupportedFaultBOOLBaseIDFaultBOOLFlashUpdateRequiredBOOLSelfTestFaultBOOLDiagBits_Pad14BOOLDiagBits_Pad15BOOLPadINT4LocalClockOffsetLINT8LocalClockOffsetTimestampLINT8GrandMasterClockID[8]SINT8ChannelMode00SINT1ChannelMode01SINT1ChannelMode02SINT1ChannelMode03SINT1PadINT4Ch00Diagnostic Digital with Diagnostics Channel (Configurable)48Ch01Diagnostic Digital with Diagnostics Channel (Configurable)48Ch02Diagnostic Digital with Diagnostics Channel (Configurable)48Ch03Diagnostic Digital with Diagnostics Channel (Configurable)48
- Diagnostic Digital Configurable 8 Point with Diagnostics Assembly B- Instance ID = 0x801C (32,796)
- Size = 200 bytes
 Diagnostic Assembly Instance – 32,796NameData TypeSize in BytesChannelMode04SINT1ChannelMode05SINT1ChannelMode06SINT1ChannelMode07SINT1PadINT4Ch04See Diagnostic Digital with Diagnostics Channel (Configurable)48Ch05See Diagnostic Digital with Diagnostics Channel (Configurable)48Ch06See Diagnostic Digital with Diagnostics Channel (Configurable)48Ch07See Diagnostic Digital with Diagnostics Channel (Configurable)48
Diagnostic Counters
            Diagnostic Counters Assembly for I/O
- Instance ID = 0x301 (769)
- Size = 16 bytes
| Name | Data Type | Size in Bytes | 
|---|---|---|
| RunMode | BOOL | 1 | 
| InfoBits_Pad1 | BOOL | |
| DiagnosticActive | BOOL | |
| InfoBits_Pad3 | BOOL | |
| InfoBits_Pad4 | BOOL | |
| InfoBits_Pad5 | BOOL | |
| InfoBits_Pad6 | BOOL | |
| InfoBits_Pad7 | BOOL | |
| DiagnosticSequenceCount | SINT | 1 | 
| CIPConnections | INT | 2 | 
| CIPLostPackets | DINT | 4 | 
| CIPTimeouts | DINT | 4 | 
| CPUUtilization | INT | 2 | 
| Pad | INT | 2 | 
Provide Feedback