Safety Output Module Safety Data
    | Attribute | Point Operation Type | |
|---|---|---|
| Single Channel | Dual Channel | |
| Total Failure Rate (λ (safety related)) | 4.00535E-06 | 4.09320E-06 | 
| Safe Failure Fraction (SFF) | 99.997% | 99.997% | 
| Safe Failure Rate (λ S) | 2.00268E-06 | 2.04659E-06 | 
| Diagnostic Coverage (DC) | 99.993% | 99.994% | 
| Safe Detected Failure Rate (λ SD) | 2.00254E-06 | 2.04647E-06 | 
| Safe Undetected Failure Rate (λ SU) | 1.31748E-10 | 1.21184E-10 | 
| Dangerous Failure Rate (λ D) | 2.00268E-06 | 2.04660E-06 | 
| Dangerous Detected Failure Rate (λ DD) | 2.00254E-06 | 2.04648E-06 | 
| Dangerous Undetected Failure Rate (λ DU) | 1.31748E-10 | 1.21184E-10 | 
| Diagnostic Test Interval (DTI) (hours) | 8 | 8 | 
| Hardware Fault Tolerance (HFT) | 0 | 1 | 
| Spurious Trip Rate (STR) | 3.366E-06 | 3.874E-06 | 
| Mean Time to Failure, Spurious (MTTF-spurious), (hours) | 297048 | 258134 | 
| PFH (1/hours) | 1.317E-10 | 1.212E-10 | 
| PFD avg, at Mission Time of 20 years | 1.154E-05 | 1.062E-05 | 
| Safety Reaction Time (SRT), (millisecond) | 6 | 6 | 
| Mean Time to Fail Dangerous (MTTF D) =
                                    1/λ D Mean Time to Repair (MTTR) is 8 Hours = DTI 
     IMPORTANT: 
     Faulty module is non-repairable and must be replaced with
                                            a new module within MTTR. | ||