Use the Status Indicators for Troubleshooting
    PointMax I/O modules use the following status indicators: 
- SA Power Indicator - This indicator operates the same for all PointMax I/O modules.
- Module Status Indicator - This indicator operates the same for all PointMax I/O modules.
- Point Status Indicator - This indicator operates differently based on the module type you are using.
SA Power Status Indicator
            
  | Indicator State | Description | Recommended Action | 
|---|---|---|
| Off | The module is not powered. A safety connection cannot be made or maintained. | Complete the following actions: 
 | 
| Steady green | There is SA power to the module | None | 
| Steady red | 
 A safety connection cannot be made or maintained. | Complete the following actions: 
 | 
Module Status Indicators
            
  | Indicator State | Description | Recommended Action | 
|---|---|---|
| Off | The module is not powered. | Complete the following actions: 
 | 
| Steady green | The module has a connection to a controller and is operating normally. | None | 
| Flashing green | One of the following conditions exist: 
 | Complete the following actions: 
 | 
| Steady red | The module experienced a nonrecoverable fault. | Complete the following actions: 
 | 
| Flashing red | One of the following conditions exist: 
 | Complete one of the following: 
 | 
| Flashing red/green | This pattern indicates that a UNID for the safety device needs to be
                  configured. | None | 
Point Status Indicators - Safety Digital I/O Modules
      
  | Indicator State | Description | Recommended Action | 
|---|---|---|
| Off | One of the following:
                   
 | One of the following:
                   
 | 
| Steady yellow | The point is On. | None | 
| Flashing red | The module experienced one or more recoverable faults. | Locate and correct the faults. | 
| Steady red | One of the following:
                   
 | One of the following:
                   
 | 