Diagnostic Channel
    This data type is retrieved as part of the diagnostic assembly instance.
- Diagnostic Digital Diagnostics Safety Channel with Demand (Input)- Size = 72 bytes
 Structure for Diagnostic Digital Diagnostics Safety Channel with Demand (Input)NameData TypeSize in BytesDataBits_Pad0BOOL2FaultBOOLUncertainBOOLDataBits_Pad3BOOLShortCircuitBOOLDataBits_Pad5BOOLFieldPowerOffBOOLDataBits_Pad7BOOLDataBits_Pad8BOOLDataBits_Pad9BOOLDataBits_Pad10BOOLDataBits_Pad11BOOLDataBits_Pad12BOOLDataBits_Pad13BOOLDataBits_Pad14BOOLDataBits_Pad15BOOLInternalFaultBOOL2OverTemperatureBOOLCriticalTemperatureBOOLDiagBits_Pad3BOOLDiagBits_Pad4BOOLDiagBits_Pad5BOOLDiagBits_Pad6BOOLDiagBits_Pad7BOOLDiagBits_Pad8BOOLDiagBits_Pad9BOOLDiagBits_Pad10BOOLDiagBits_Pad11BOOLDiagBits_Pad12BOOLDiagBits_Pad13BOOLDiagBits_Pad14BOOLDiagBits_Pad15BOOLPadDINT4ShortCircuitTimestampLINT8InternalFaultTimestampLINT8FieldPowerOnTimestampLINT8FieldPowerOffTimestampLINT8OverTemperatureTimestampLINT8CriticalTemperatureTimestampLINT8OnToOffTimestampLINT8OffToOnTimestampLINT8
- Diagnostic Digital Safety Diagnostics 2 Input Channel (Output)- Size = 88 bytes
 Structure for Diagnostic Digital Safety Diagnostics 2 Input Channel (Output)NameData TypeSize in BytesDataBits_Pad0BOOL2FaultBOOLUncertainBOOLNoLoadBOOLShortCircuitBOOLDataBits_Pad5BOOLFieldPowerOffBOOLDataBits_Pad7BOOLDualChannelFaultBOOLDataBits_Pad9BOOLDataBits_Pad10BOOLDataBits_Pad11BOOLDataBits_Pad12BOOLDataBits_Pad13BOOLDataBits_Pad14BOOLDataBits_Pad15BOOLInternalFaultBOOL2OverloadBOOLShortCircuitGroundBOOLOverTemperatureBOOLCriticalTemperatureBOOLDiagBits_Pad5BOOLDiagBits_Pad6BOOLDiagBits_Pad7BOOLDiagBits_Pad8BOOLDiagBits_Pad9BOOLDiagBits_Pad10BOOLDiagBits_Pad11BOOLDiagBits_Pad12BOOLDiagBits_Pad13BOOLDiagBits_Pad14BOOLDiagBits_Pad15BOOLPadDINT4NoLoadTimestampLINT8ShortCircuitTimestampLINT8DualChannelFaultTimestampLINT8InternalFaultTimestampLINT8OverloadTimestampLINT8ShortCircuitGroundTimestampLINT8FieldPowerOnTimestampLINT8FieldPowerOffTimestampLINT8OverTemperatureTimestampLINT8CriticalTemperatureTimestampLINT8
Provide Feedback