Calibration Instrumentation Specifications
    When you calibrate the analog input modules, send current or ohms reference signals
                to the module to calibrate it. To maintain your module's factory calibration
                accuracy, use the instrumentation with the specifications listed in the following
                    table.
    
    
     IMPORTANT: 
    Do not calibrate your module
                    with an instrument that is less accurate than those specified in following
                    table. The following events can result:
- Calibration appears to occur normally but the module gives inaccurate data during operation.
- A calibration fault occurs, forcing you to abort calibration. When this happens, I.Chxx.CalFault tag is set for the channel you attempted to calibrate. You can clear this tag by completing a valid calibration or cycling power to the module.
| Catalog Number | Channel Input Type | Calibration Instrumentation Specifications | 
|---|---|---|
| 5034-IRT4I and 5034-IRT4IXT | RTD | 1.0…448.0 Ω resistors ±0.01% | 
| Thermocouple (mV) | 0…100 mV source ±0.5 µV | 