Module-defined Data Types (PowerFlex 700SE via Virtual Backplane)

The tables below list and describe the Input and Output module-defined data types for this module. These values apply to all three voltage classes of the PowerFlex 700SE drive (i.e., 200V, 400V, and 600V).
Module-defined Data Type: AB:ENHANCED_DRIVE_GENERIC:I:0
Comm Format: User-defined
Member Name
Bit in Previous Word
Data Type
Default Display Style
Drive Parameter
LogicStatus
DINT
Binary
155
Enabled
0**
BOOL
Decimal
155.0
Running
1**
BOOL
Decimal
155.1
ActualDir
3**
BOOL
Decimal
155.3
Accelerating
4
BOOL
Decimal
155.4
Decelerating
5
BOOL
Decimal
155.5
Jogging
6
BOOL
Decimal
155.6
Faulted
7**
BOOL
Decimal
155.7
Alarm
8**
BOOL
Decimal
155.8
FlashMode
9**
BOOL
Decimal
155.9
RunReady
10
BOOL
Decimal
155.10
AtLimit
11
BOOL
Decimal
155.11
TachLossSw
12
BOOL
Decimal
155.12
AtZeroSpd
13
BOOL
Decimal
155.13
MCEnAck
18
BOOL
Decimal
155.18
MCCommis
19
BOOL
Decimal
155.19
PscSystemReady
20
BOOL
Decimal
155.20
CommandRun
26
BOOL
Decimal
155.26
UserDefinedRealData
REAL[12]
Float
User-defined
UserDefinedIntegerData
DINT[3]
Decimal
User-defined
Module-defined Data Type: AB:ENHANCED_DRIVE_GENERIC:O:0
Comm Format: User-defined
Member Name
Bit in Previous Word
Data Type
Default Display Style
Drive Parameter
Description
LogicCommand
DINT
Binary
151
TachLossRst
2
BOOL
Decimal
151.2
Commands the drive to use the primary speed feedback device following a failure of that device which would have caused to drive to use an alternate device or method for feedback.
MCAtuneEn
4
BOOL
Decimal
151.4
Enables Motor Control Autotune to run upon the next Start command.
PwrDiagEn
5
BOOL
Decimal
151.5
Enables the testing of power components including voltage sensor, current sensor, grounding, power devices.
DirCtrlEn
6
BOOL
Decimal
151.6
If enabled, the "normal" forward direction becomes reverse and vice versa.
PMOffsetEn
7
BOOL
Decimal
151.7
Enables test to measure offset angle of encoder for PM motors.
NormalStop
16
BOOL
Decimal
*Logic Parser
Commands the drive to perform a controlled stop, including the ramp and S-curve functions, if enabled.
Start
17
BOOL
Decimal
*Logic Parser
Commands the drive to start. Start may be latched or unlatched, see P153.
Jog1
18
BOOL
Decimal
*Logic Parser
Commands the drive to run at the Jog 1 speed as long as this input is active.
ClearFault
19
BOOL
Decimal
*Logic Parser
Requests the drive to clear all faults. If any faults conditions are still present, fault will again be asserted.
CurrLimStop
24
BOOL
Decimal
*Logic Parser
Commands the drive to perform a current limit stop.
CoastStop
25
BOOL
Decimal
*Logic Parser
Commands the drive to coast to a stop.
PscSystemReset
BOOL
Decimal
UserDefinedRealData
REAL[12]
Float
User-defined
User-defined Real Data
UserDefinedIntegerData
DINT[3]
Decimal
User-defined
User-defined Integer Data
* The output from the Logic Parser is mapped to parameter 152, bits 16-31.
Module-defined Data Type: AB:DRIVE_CUSTOMUSER_DEFINED:I:0
Comm Format: Custom User-defined Control
Member Name
Bit in Previous Word
Data Type
Default Display Style
Drive Parameter
Description
LogicStatus
DINT
Binary
Logic Status
UserDefinedRealData
REAL[8]
Float
User-defined
User-defined Real Data
UserDefinedIntegerData
DINT[7]
Decimal
User-defined
User-defined Integer Data
Module-defined Data Type: AB:DRIVE_CUSTOMUSER_DEFINED:O:0
Comm Format: Custom User-defined Control
Member Name
Bit in Previous Word
Data Type
Default Display Style
Drive Parameter
Description
LogicCommand
DINT
Binary
Logic Command
UserDefinedRealData
REAL[8]
Float
User-defined
User-defined Real Data
UserDefinedIntegerData
DINT[7]
Decimal
User-defined
User-defined Integer Data
Provide Feedback
Have questions or feedback about this documentation? Please submit your feedback here.