Module-defined Data Types (PowerFlex 70 via 20-COMM-C or 20-COMM-E)

The tables below list and describe the Input and Output module-defined data types for this module.
Input Data Types
Comm Format: Data
Data Links
Data Type
0
AB:PowerFlex70_Drive_8Bytes:I:0
2
AB:PowerFlex70_Drive_12Bytes:I:0
4
AB:PowerFlex70_Drive_16Bytes:I:0
6
AB:PowerFlex70_Drive_20Bytes:I:0
8
AB:PowerFlex70_Drive_24Bytes:I:0
Member Name
Bit in
Previous Word
Data Type
Default Display Style
DPI Description
Drive Parameter
DriveStatus
INT
Binary
Drive Status
209
Ready
0
BOOL
Decimal
Ready
209.0
Active
1
BOOL
Decimal
Active
209.1
CommandDir
2
BOOL
Decimal
Command Dir
209.2
ActualDir
3
BOOL
Decimal
Actual Dir
209.3
Accelerating
4
BOOL
Decimal
Accelerating
209.4
Decelerating
5
BOOL
Decimal
Decelerating
209.5
Alarm
6
BOOL
Decimal
Alarm
209.6
Faulted
7
BOOL
Decimal
Faulted
209.7
AtSpeed
8
BOOL
Decimal
At Speed
209.8
LocalID0
9
BOOL
Decimal
Local ID 0
209.9
LocalID1
10
BOOL
Decimal
Local ID 1
209.10
LocalID2
11
BOOL
Decimal
Local ID 2
209.11
SpdRefID0
12
BOOL
Decimal
Spd Ref ID 0
209.12
SpdRefID1
13
BOOL
Decimal
Spd Ref ID 1
209.13
SpdRefID2
14
BOOL
Decimal
Spd Ref ID 2
209.14
SpdRefID3
15
BOOL
Decimal
Spd Ref ID 3
209.15
OutputFreq
INT
Decimal
Output Freq
1
UserDefinedData
INT[8]
Decimal
User-defined Data
User-defined
Output Data Types
Comm Format: Data
Data Links
Data Type
0
AB:PowerFlex70_Drive_4Bytes:O:0
2
AB:PowerFlex70_Drive_8Bytes:O:0
4
AB:PowerFlex70_Drive_12Bytes:O:0
6
AB:PowerFlex70_Drive_16Bytes:O:0
8
AB:PowerFlex70_Drive_20Bytes:O:0
Member Name
Bit in Previous Word
Data Type
Default Display Style
DPI Description
Drive Parameter
DriveLogicRslt
INT
Binary
Drive Status 1
271
Stop
0
BOOL
Decimal
Stop
271.0
Start
1
BOOL
Decimal
Start
271.1
Jog
2
BOOL
Decimal
Jog
271.2
ClearFault
3
BOOL
Decimal
Clear Fault
271.3
Forward
4
BOOL
Decimal
Forward
271.4
Reverse
5
BOOL
Decimal
Reverse
271.5
LocalContrl
6
BOOL
Decimal
Local Contrl
271.6
MOPInc
7
BOOL
Decimal
MOP Inc
271.7
Accel1
8
BOOL
Decimal
Accel 1
271.8
Accel2
9
BOOL
Decimal
Accel 2
271.9
Decel1
10
BOOL
Decimal
Decel 1
271.10
Decel2
11
BOOL
Decimal
Decel 2
271.11
SpdRefID0
12
BOOL
Decimal
Spd Ref ID 0
271.12
SpdRefID1
13
BOOL
Decimal
Spd Ref ID 1
271.13
SpdRefID2
14
BOOL
Decimal
Spd Ref ID 2
271.14
MOPDec
15
BOOL
Decimal
MOP Dec
271.15
CommandedFreq
INT
Decimal
Commanded Freq
2
UserDefinedData
INT[8]
Decimal
User-defined Data
User-defined
Provide Feedback
Have questions or feedback about this documentation? Please submit your feedback here.
Normal