Module-defined Data Types (8720SpindleDrive)

The tables below list and describe the Input and Output module-defined data types for this module.
Input Data Types
Member Name
Bit in
Previous Word
Data Type
Default Display Style
SCANPort Description
LogicStatus
INT
Binary
Logic Status
Enabled
0
BOOL
Binary
Enabled
AutoEnabled
1
BOOL
Binary
Auto Enabled
RotationDirection
2
BOOL
Binary
Rotation Direction
DriveOK
3
BOOL
Binary
Drive OK
ZeroSpeed
4
BOOL
Binary
Zero Speed
AtSpeed
5
BOOL
Binary
At Speed
OrientComplete
6
BOOL
Binary
Orient Complete
Not Used
7
BOOL
Binary
Not Used
BrakeEnable
8
BOOL
Binary
Brake Enable
TorqueLimit
9
BOOL
Binary
Torque Limit
HiWindingSelected
10
BOOL
Binary
Hi Winding Selected
LoWindingSelected
11
BOOL
Binary
Lo Winding Selected
ShutdownFault
12
BOOL
Binary
Shutdown Fault
Not Used
13
BOOL
Binary
Not Used
Not Used
14
BOOL
Binary
Not Used
ManualMode
15
BOOL
Binary
Manual Mode
Feedback
INT
Decimal
Feedback
UserDefinedData
INT[8]
Decimal
User-defined Data
Output Data Types
Member Name
Bit in
Previous Word
Data Type
Default Display Style
SCANPort Description
LogicCommand
INT
Binary
Logic Command
RegenStop
0
BOOL
Binary
Regen Stop
Start
1
BOOL
Binary
Start
Jog
2
BOOL
Binary
Jog
ClearFaults
3
BOOL
Binary
Clear Faults
CoastStop
4
BOOL
Binary
Coast Stop
ParamSetSelect
5
BOOL
Binary
Param Set Select
ParamSetStrobe
6
BOOL
Binary
Param Set Strobe
Home
7
BOOL
Binary
Home
Manual
8
BOOL
Binary
Manual
Reference
INT
Decimal
Reference
UserDefinedData
INT[8]
Decimal
User-defined Data
Provide Feedback
Have questions or feedback about this documentation? Please submit your feedback here.