Module-defined Data Types (150-SMC Flex-C)

The tables below list and describe the Input and Output module-defined data types for this module.
Input Data Types
Data Links
Data Type
0
AB:150SMCFlex_8Bytes:I:0
2
AB:150SMCFlex_12Bytes:I:0
4
AB:150SMCFlex_16Bytes:I:0
6
AB:150SMCFlex_20Bytes:I:0
8
AB:150SMCFlex_24Bytes:I:0
Member Name
Bit in
Previous Word
Data Type
Default Display Style
DPI Description
LogicStatus
INT
Binary
Logic Status
Enabled
0
BOOL
Decimal
Enabled
Running
1
BOOL
Decimal
Running
Phasing
2
BOOL
Decimal
Phasing
PhasingActive
3
BOOL
Decimal
Phasing Active
Starting
4
BOOL
Decimal
Starting
Stopping
5
BOOL
Decimal
Stopping
Alarm
6
BOOL
Decimal
Alarm
Fault
7
BOOL
Decimal
Fault
AtSpeed
8
BOOL
Decimal
At Speed
Start
9
BOOL
Decimal
Start
ByPass
10
BOOL
Decimal
Bypass
Ready
11
BOOL
Decimal
Ready
Output Data Types
Data Links
Data Type
0
AB:150SMCFlex_4Bytes:O:0
2
AB:150SMCFlex_8Bytes:O:0
4
AB:150SMCFlex_12Bytes:O:0
6
AB:150SMCFlex_16Bytes:O:0
8
AB:150SMCFlex_20Bytes:O:0
Member Name
Bit in
Previous Word
Data Type
Default Display Style
DPI Description
LogicCommand
INT
Binary
Logic Command
Stop
0
BOOL
Decimal
Stop
Start
1
BOOL
Decimal
Start
Option1Command
2
BOOL
Decimal
Option 1 Command
ClearFault
3
BOOL
Decimal
Clear Fault
Option2Command
4
BOOL
Decimal
Option 2 Command
Provide Feedback
Have questions or feedback about this documentation? Please submit your feedback here.