Module-defined Data Types (1397DigitalDCDrive-CN1)

The tables below list and describe the Input and Output module-defined data types for this module.
Input Data Types
Data Links
Data Type
0
AB:1397_Drive_8Bytes:I:0
2
AB:1397_Drive_12Bytes:I:0
4
AB:1397_Drive_16Bytes:I:0
6
AB:1397_Drive_20Bytes:I:0
8
AB:1397_Drive_24Bytes:I:0
Member Name
Bit in
Previous Word
Data Type
Default Display Style
DPI Description
LogicStatus
INT
Binary
Logic Status
Ready
0
BOOL
Decimal
Ready
Active
1
BOOL
Decimal
Active
CommandDir
2
BOOL
Decimal
Command Dir
ActualDir
3
BOOL
Decimal
Actual Dir
Accelerating
4
BOOL
Decimal
Accelerating
Decelerating
5
BOOL
Decimal
Decelerating
Alarm
6
BOOL
Decimal
Alarm
Faulted
7
BOOL
Decimal
Faulted
AtSpeed
8
BOOL
Decimal
At Speed
LocalID0
9
BOOL
Decimal
Local ID 0
LocalID1
10
BOOL
Decimal
Local ID 1
LocalID2
11
BOOL
Decimal
Local ID 2
SpdRefID0
12
BOOL
Decimal
Spd Ref ID 0
SpdRefID1
13
BOOL
Decimal
Spd Ref ID 1
SpdRefID2
14
BOOL
Decimal
Spd Ref ID 2
SpdRefID3
15
BOOL
Decimal
Spd Ref ID 3
SpeedFeedback
INT
Decimal
Speed Feedback
UserDefinedData
INT[8]
Decimal
User Defined Data
Output Data Types
Data Links
Data Type
0
AB:1397_Drive_4Bytes:O:0
2
AB:1397_Drive_8Bytes:O:0
4
AB:1397_Drive_12Bytes:O:0
6
AB:1397_Drive_16Bytes:O:0
8
AB:1397_Drive_20Bytes:O:0
Member Name
Bit in
Previous Word
Data Type
Default Display Style
DPI Description
LogicCommand
INT
Binary
Logic Command
Stop
0
BOOL
Decimal
Stop
Start
1
BOOL
Decimal
Start
Jog
2
BOOL
Decimal
Jog
ClearFault
3
BOOL
Decimal
Clear Fault
Forward
4
BOOL
Decimal
Forward
Reverse
5
BOOL
Decimal
Reverse
LocalControl
6
BOOL
Decimal
Local Contrl
MOPInc
7
BOOL
Decimal
MOP Inc
Accel1
8
BOOL
Decimal
Accel 1
Accel2
9
BOOL
Decimal
Accel 2
Decel1
10
BOOL
Decimal
Decel 1
Decel2
11
BOOL
Decimal
Decel 2
SpdRefID0
12
BOOL
Decimal
Spd Ref ID 0
SpdRefID1
13
BOOL
Decimal
Spd Ref ID 1
SpdRefID2
14
BOOL
Decimal
Spd Ref ID 2
MOPDec
15
BOOL
Decimal
MOP Dec
SpeedReference
INT
Decimal
Speed Reference
UserDefinedData
INT[8]
Decimal
User Defined Data
Provide Feedback
Have questions or feedback about this documentation? Please submit your feedback here.
Normal