Module-defined Data Types (1336R-REGENBrake-CN1)

The tables below list and describe the Input and Output module-defined data types for this module.
Input Data Types
Data Links
Data Type
0
AB:1336REGEN_SP_Drive_8Bytes:I:0
2
AB:1336REGEN_SP_Drive_12Bytes:I:0
4
AB:1336REGEN_SP_Drive_16Bytes:I:0
6
AB:1336REGEN_SP_Drive_20Bytes:I:0
8
AB:1336REGEN_SP_Drive_24Bytes:I:0
Member Name
Bit in
Previous Word
Data Type
Default Display Style
SCANPort Description
Drive Parameter
LogicStatus
INT
Binary
Logic Status
26
Ready
0
BOOL
Decimal
Ready
26.0
Enabled
1
BOOL
Decimal
Enabled
26.1
Warning
6
BOOL
Decimal
Warning
26.6
Faulted
7
BOOL
Decimal
Faulted
26.7
Feedback
INT
Decimal
Feedback
Output Data Types
Data Links
Data Type
0
AB:1336REGEN_SP_Drive_4Bytes:O:0
2
AB:1336REGEN_SP_Drive_8Bytes:O:0
4
AB:1336REGEN_SP_Drive_12Bytes:O:0
6
AB:1336REGEN_SP_Drive_16Bytes:O:0
8
AB:1336REGEN_SP_Drive_20Bytes:O:0
Member Name
Bit in
Previous Word
Data Type
Default Display Style
SCANPort Description
Drive Parameter
CommandStatus
INT
Binary
Command Status
25
NormalStop
0
BOOL
Decimal
Normal Stop
25.0
Enable
1
BOOL
Decimal
Enable
25.1
ClearFault
3
BOOL
Decimal
Clear Fault
25.3
Reset
15
BOOL
Decimal
Reset
25.15
Reference
INT
Decimal
Reference
None