Module Data Types - 1794-OF4I

The table below lists and describes module-defined data types for the 1794-OF4I analog output module. It includes information for input (as indicated by an "I"), output (as indicated by an "O"), and configuration (as indicated by a "C").
TIP:
The OutputEnable configuration data type must be set to 1 in order for the Hold For Initialization feature to function. This value can be set in the Data Monitor from the Controller Tags window, or by using your own program. An example of the Hold For Initialization feature is outlined below.
When a communication fault or idle period is encountered, the module accepts the Safe State held by the adapter (in the SSSafeStateConfig0 and SSSafeStateConfig1 members). When communication is restored, the module’s output status is polled for each condition of output on each channel (in the Ch0OutputHeld and Ch1OutputHeld members) using the output data in the Ch0OutputReadBack and Ch1OutputReadBack members. When the output data matches the respective Ch0OutputReadBack and Ch1OutputReadBack values, the channel returns to normal operation and indicates this by clearing the Ch0OutputHeld and Ch1OutputHeld members. The members identified in this example are defined in the tables below.
TIP:
FLEX I/O is based on 16-bit INTs and not 32-bit DINTs. This may decrease performance with certain instructions
Module-defined Data Type: AB:1794_OF4I:I:0
Member Name
Type
Default
Display Style
Description
Ch0ReadBack
Ch1ReadBack
Ch2ReadBack
Ch3ReadBack
INT
Decimal
Read back data for output on a channel. During a communication fault or idle period, it contains real time output data as well as any Safe State values sent by the adapter.
InputData1
INT
Binary
Contains input status.
CalibrationDone
BOOL
Decimal
Set to 1 after calibration cycle completed.
CalibrationBad
BOOL
Decimal
Set to 1 if channel calibration coefficients cannot be saved or read properly.
ConfigurationMode
BOOL
Decimal
Set to 1 when configuration mode is selected. The module status indicator flashes when set.
FieldPowerOff
BOOL
Decimal
Set to 1 when the 24V field power fails. The module status indicator flashes when set.
PowerUp
BOOL
Decimal
This member is set when data in the configuration tag is all zeros due to reset or a cleared data type in the configuration tag. The module status indicator flashes when set.
InputData2
INT
Binary
Contains input status.
Ch0OpenWire
Ch1OpenWire
Ch2OpenWire
Ch3OpenWire
BOOL
Decimal
Indicates the corresponding current output channel is open.
Ch0Held
Ch1Held
Ch2Held
Ch3Held
BOOL
Decimal
Indicates that the output is holding at the level in the readback data for the respective channel during output enable. These data types return to 0 when the output data matches the readback.
Module-defined Data Type: AB:1794_OF4I:O:0
Member Name
Type
Default
Display Style
Description
SafeStateConfig0
SafeStateConfig1
BOOL
Decimal
Designates the source of the safe state data when output enable is 0.
OutputEnable
BOOL
Decimal
Always keep this member set to 1. It must be a 1 in order for the Hold Outputs feature to function.
Ch0Data
INT
Decimal
Output data for channel 0. The output data is real time data formatted to the selected configuration.
Ch1Data
INT
Decimal
Output data for channel 1. The output data is real time data formatted to the selected configuration.
Ch2Data
INT
Decimal
Output data for channel 2. The output data is real time data formatted to the selected configuration.
Ch3Data
INT
Decimal
Output data for channel 3. The output data is real time data formatted to the selected configuration.
Module-defined Data Type: AB:1794_OF4I:C:0
Member Name
Type
Default
Display Style
Description
OutputConfiguration
INT
Binary
Ch0Calibrate
Ch1Calibrate
Ch2Calibrate
Ch3Calibrate
BOOL
Decimal
Includes a channel in calibration when selected.
GainOffsetCalibration
BOOL
Decimal
Holds the High or Low Reference settings you selected on the Input Configuration tab from the Module Properties dialog box.
CalibrationClock
BOOL
Decimal
If selected, calibration mode starts and calibration settings for the selected channels are accepted.
If clear, the accepted current calibration coefficients are stored to selected channels, applied and calibration mode is exited.
QuickCalibration
BOOL
Decimal
If set to 1, calibration coefficient is stored to all related configurations for selected channels.
Ch0Hold
Ch1Hold
Ch2Hold
Ch3Hold
BOOL
Decimal
If set, when a 1 to 0 to 1 transition of the OutputEnable member, hold output level on a channel until the real time output data equals the level.
InterleaveInterrupts
BOOL
Decimal
If set, ensures exchange of time critical data when channels are configured for the fastest update times. Do not check the
Interleave Module Interrupts
check box unless you know you have a specific use for this option. The Interleave Module Interrupts feature is useful only in limited circumstances and can
only
be enabled when you configured a module’s Conversion Rate to
1200 Hz
, Low Pass Time Constant to
None
, and Real Time Sampling period to
0
for
ALL
channels on the module.
Transparent
BOOL
Decimal
If set, permits configuration to be changed without using the InitiateConfiguration data type.
InitiateConfiguration
BOOL
Decimal
If set, instructs the module to enter configuration mode. When transition to 0 occurs, configuration is applied and any subsequent configuration is ignored until this member is toggled.
SSSafeStateConfig0
BOOL
Decimal
Safe state value to use for SSSafeStateConfig0.
SSSafeStateConfig1
BOOL
Decimal
Safe state value to use for SSSafeStateConfig1.
SSOutputEnable
BOOL
Decimal
Safe state value to use for SSOutputEnable.
SSCh0Data
SSCh1Data
SSCh2Data
SSCh3Data
INT
Decimal
Safe State value to use for selected channel.