Module-defined Data Types (1305-ACDrive-CN1, 1336F-PLUSIIDrive-CN1, 1336S-PLUSDriveLG-CN1 and PLUSDriveSM-CN1)

The tables below list and describe the Input and Output module-defined data types for these modules.
Input Data Types
Data Links
Data Type
0
AB:StandardSCANport_Drive_8Bytes:I:0
2
AB:StandardSCANport_Drive_12Bytes:I:0
4
AB:StandardSCANport_Drive_16Bytes:I:0
6
AB:StandardSCANport_Drive_20Bytes:I:0
8
AB:StandardSCANport_Drive_24Bytes:I:0
Member Name
Bit in
Previous Word
Data Type
Default Display Style
ScanPort
Description
Drive Parameter
DriveStatus
(DriveStatus1 for 1336F-PLUSIIDrive)
INT
Binary
Drive Status
59
Enabled
0
BOOL
Decimal
Enabled
59.0
Running
1
BOOL
Decimal
Running
59.1
CommandFwd
2
BOOL
Decimal
Command Fwd
59.2
RotatingFwd
3
BOOL
Decimal
Rotating Fwd
59.3
Accel
4
BOOL
Decimal
Accel
59.4
Decel
5
BOOL
Decimal
Decel
59.5
Alarm
6
BOOL
Decimal
Alarm
59.6
Faulted
7
BOOL
Decimal
Faulted
59.7
AtSpeed
8
BOOL
Decimal
At Speed
59.8
Local0
9
BOOL
Decimal
Local 0
59.9
Local1
10
BOOL
Decimal
Local 1
59.10
Local2
11
BOOL
Decimal
Local 2
59.11
FreqRef0
12
BOOL
Decimal
Freq Ref 0
59.12
FreqRef1
13
BOOL
Decimal
Freq Ref 1
59.13
FreqRef2
14
BOOL
Decimal
Freq Ref 2
59.14
FreqRef3
15
BOOL
Decimal
Freq Ref 3
59.15
OutputFreq
INT
Decimal
Output Freq
66
UserDefinedData
INT[8]
Decimal
User-defined Data
User-defined
Output Data Types
Data Links
Data Type
0
AB:StandardSCANport_Drive_4Bytes:O:0
2
AB:StandardSCANport_Drive_8Bytes:O:0
4
AB:StandardSCANport_Drive_12Bytes:O:0
6
AB:StandardSCANport_Drive_16Bytes:O:0
8
AB:StandardSCANport_Drive_20Bytes:O:0
Member Name
Bit in
Previous Word
Data Type
Default Display Style
SCANPort
Description
Drive Parameter
LogicCommand
INT
Binary
Logic Command
None
Stop
0
BOOL
Decimal
Stop
Start
1
BOOL
Decimal
Start
Jog
2
BOOL
Decimal
Jog
ClearFaults
3
BOOL
Decimal
Clear Faults
Direction0
4
BOOL
Decimal
Direction 0
Direction1
5
BOOL
Decimal
Direction 1
Local
6
BOOL
Decimal
Local
MOPIncrement
7
BOOL
Decimal
MOP Increment
AccelTimeA
8
BOOL
Decimal
Accel Time A
AccelTimeB
9
BOOL
Decimal
Accel Time B
DecelTimeA
10
BOOL
Decimal
Decel Time A
DecelTimeB
11
BOOL
Decimal
Decel Time B
ReferenceSelect0
12
BOOL
Decimal
Reference Select 0
ReferenceSelect1
13
BOOL
Decimal
Reference Select 1
ReferenceSelect2
14
BOOL
Decimal
Reference Select 2
MOPDecrement
15
BOOL
Decimal
MOP Decrement
FreqCommand
INT
Decimal
Freq Command
65
UserDefinedData
INT[8]
Decimal
User-defined Data
User-defined
Provide Feedback
Have questions or feedback about this documentation? Please submit your feedback here.