Configuration Errors - 1794-VHSC

Bits in the Status member are not named because they may have 3 different interpretations, depending on the module operating mode as described below.
The Status Word bit values and bit definitions depend on the state of the VHSC. There are three reporting states:
  • Normal operation (Status LED-solid green)
  • Incomplete, incorrect, or conflicting configuration (Status LED-flashing green)
  • Hardware power up self-test error (Status LED-flashing red). Refer to
    1794-VHSC Hardware Power Up Self-Test Errors
    for more information.
The ConfigurationError member of the AB:1794_VHSC:I:0 module-defined data type reflects a change in its members values any time incomplete, incorrect, or conflicting configuration data is sent to the module. Use the table below to understand the reasons for module’s condition.
Important:
If the controller is in Run mode and a bad configuration is sent to the 1794-VHSC module, the error flags are set in the Fault word in the Input tags and the green OK LED on the module will blink On and Off. The module, however, will continue to run with its previous good data. To avoid confusing the monitoring application, no live data is returned to the
Logix Designer
application.
Status (Bit Definitions)
Meaning in This Context
Status (Bit Definitions)
Description
Fault.0
Ch0Zinput
Fault.0
Reserved Configuration or mode was set.
Fault.1
Ch0ZeroFrequencyDetect
Fault.1
ZeroFrequency set, B Filter and A Filter were selected and no Filter Rate was specified, or multiple filters were selected (should not be enterable via HI, but possible via tags.)
Fault.2
Ch0StoredData2
Fault.2
A timebase was entered (in the Configuration Tag) that was not a multiple of 10, or the timebase is too large (>3000 ms, >3 sec)
Fault.3
Ch0StoredData3
Fault.3
A configuration requiring a timebase was selected and no gate interval was set or the gate interval is too large (> 3 sec) or the product of timebase and gate interval is too large (> 3 sec)
Fault.4
Ch1Zinput
Fault.4
A rollover of zero was programmed through PWM was not selected or a rollover was programmed and PWM was selected, or the rollover is out of range (1 <= rollover <= 16,777,216)
Fault.5
Ch1ZeroFrequencyDetect
Fault.5
The preset is out of range (0 <= preset <= 16,777,215)
Fault.6
Ch1StoredData6
Fault.6
A configuration requiring a scalar was selected, and no scalar was programmed
or multiple scalars were selected
Fault.7
Ch1StoredData7
Fault.7
A tie has been connected to an unprogrammed window
Fault.8
Output0
Fault.8
Counter 0 window ON and OFF values are equal and not zero or Counter 0 Window ON and OFF value greater than 16,777,215
Fault.9
Output1
Fault.9
Counter 1 window ON and OFF values are equal and not zero or Counter 1 Window ON and OFF value greater than 16,777,215
Fault.10
Output2
Fault.10
N/A
Fault.11
Output3
Fault.11
Fault.12
TestFail
Fault.12
Fault.13
NotReady
Fault.13
Fault.14
FieldPowerFault
Fault.14
Fault.15
ConfigurationError
Fault.15
Incomplete, incorrect, or conflicting set of configuration parameters have been sent to the module.
Provide Feedback
Have questions or feedback about this documentation? Please submit your feedback here.
Normal