Calibrate Channels -1794-IF2XOF2I FLEX I/O Analog Combo Module

WARNING:
Be extremely cautious when calibrating FLEX I/O Modules. Do not calibrate in RUN or Remote RUN mode or while using the module for control. Doing this can lead to personal injury or death, property damage or economic loss.
The RSLogix software steps you through the process of configuring your module Calibration of FLEX I/O Modules can be performed in its entirety via the Calibration tab under Module Properties.
To calibrate the channels for a FLEX I/O analog or Combo module:
  1. Right-click the mouse button on the module you want to calibrate, and select Properties.
  2. Click the Calibration tab.
    TIP:
    The Calibrate This Channel check boxes are checked by default. This means that the channel is selected for calibration. The Calibration Range column and the Input Channel column are read only and cannot be changed. They are displayed for informational purposes only.
  3. Click the Calibrate This Channel check boxes to exclude an Input channel from this calibration.
  4. Choose the Calibrate Channels in Groups or Calibrate Channels One at a Time radio buttons to control the way you want to perform calibration.
  5. Click the Start Calibration button to start the calibration process, or
  6. Click:
    • OK to accept your edits and close the dialog.
    • Cancel to delete your edits and close the dialog.
    • Apply to make your edits effective and continue editing.
    • Help for assistance with this tab.