Configure the Output Channels of the 1756-IF4FXOF2F in Floating Point Mode

Use this procedure to configure the output channels of the 1756-IF4FXOF2F in floating point mode.
  1. Select the channel button for the channel that you want to configure.
  2. Enter the appropriate scaling values for:
    • Low Signal
    • Low Engineering
    • High Signal
    • High Engineering
  3. Select the desired output range by clicking on the drop down arrow in the
    Output Range
    list box.
  4. Select the
    Hold for Initialization
    box if you want the module to hold the output signal unchanged until the output value (received from the controller) is within 0.1% of full scale of the value held.
  5. Select:
    • OK to accept your edits and close the dialog.
    • Cancel to delete your edits and close the dialog.
    • Apply to make your edits effective and continue editing.
    • Help for assistance with this tab.
Provide Feedback
Have questions or feedback about this documentation? Please submit your feedback here.
Normal