Calibration Results Low, 1756 Analog Output Modules

Use this tab to view the results of the calibration process.
If the status column displays:
Then:
OK
Select the
Next
button to continue on to the High Reference test.
Error
Recheck the wiring to the output channel, verify the correct signal is being measured, and double-check that the values you entered are valid. After confirming the signal measurement on the channel, select the
Retry
button to retry the calibration. Continued calibration errors may indicate a channel failure. To exit a calibration state where the channel will not calibrate, select the
Stop
button to cancel calibration. The calibration process does not succeed until all calibrated channels are OK.