Stop

In a sequential function chart (SFC), a stop pauses the execution of the SFC. To resume the execution of the SFC, use the SFR and SFP instructions.
Available Languages
Ladder Diagram
Not Available
Function Block
Not Available
Sequential Function Chart
stopsymbolsfc
Structured Text
Not Available
Operands
Sequential Function Chart
Operand
Type
Format
Description
Stop
SFC_STOP
tag
pauses the execution of the SFC.
Description
Each stop uses a backing tag that provides information about the stop. The following information is available via the Tags window.
If you want to
Then check or set this member
Data Type
Details
determine when the controller has reached the stop
X
BOOL
determine to which step an SFC Reset (SFR) instruction has set the SFC
Reset
BOOL
The Reset bit marks the step that will execute when an SFC Pause (SFP) instruction resumes the execution of the SFC.
  • When an SFC Reset (SFR) instruction executes, it pauses the SFC chart and sets the Reset bit of a step in the SFC.
  • To resume the execution of the SFC, execute an SFC Pause (SFP) instruction. This instruction starts the SFC at the step with the Reset bit on and then clears the Reset bit.
determine how many times a stop has become active
Count
DINT
This is
not
a count of scans of the stop. The count increments each time the stop becomes active. It increments again only after the stop goes inactive and then active again.
use one tag for the various status bits of this action
Status
DINT
For this member
Use this bit
Reset
22
X
31