Multiply (MUL)
    This information applies to the CompactLogix 5370, ControlLogix 5570, Compact GuardLogix 5370, GuardLogix 5570, Compact GuardLogix 5380, CompactLogix 5380, CompactLogix 5480, ControlLogix 5580, and GuardLogix 5580 controllers. Controller differences are noted where applicable.
When enabled, the MUL instruction and the operator '*' multiplies Source A with Source B.
Available Languages
Ladder Diagram

Function Block Diagram
Function Block Diagram supports these elements:
FBD Block

FBD Function
     TIP: 
    
 FBD Function is applicable to CompactLogix 5380, CompactLogix 5480, ControlLogix 5580, Compact GuardLogix 5380, and GuardLogix 5580 controllers only.

Structured Text
This instruction is not available in structured text. 
     TIP: 
    
Use the operator '*' in an expression to compute the same result. Refer to 
Structured Text Syntax
 for more information on the syntax of expressions and assignments within structured text.Operands
     IMPORTANT: 
    
Unexpected operation may occur if:
- Output tag operands are overwritten.
- Members of a structure operand are overwritten.
- Except when specified, structure operands are shared by multiple instructions.
There are data conversion rules for mixing numeric data types within an instruction. See Data Conversions.
Ladder Diagram
| Operand | Data Type CompactLogix 5370, ControlLogix 5570, Compact GuardLogix 5370, and GuardLogix 5570 controllers | Data Type CompactLogix 5380, CompactLogix 5480, ControlLogix 5580, Compact GuardLogix 5380, and GuardLogix 5580 controllers | Format | Description | 
|---|---|---|---|---|
| Source A | SINT INT DINT REAL | SINT INT DINT LINT USINT UINT UDINT ULINT REAL LREAL | immediate tag | Value of the multiplicand. | 
| Source B | SINT INT DINT REAL | SINT INT DINT LINT USINT UINT UDINT ULINT REAL LREAL | immediate tag | Value of the multiplier. | 
| Dest | SINT INT DINT REAL | SINT INT DINT LINT USINT UINT UDINT ULINT REAL LREAL | tag | Tag to store the result of the instruction. | 
Function Block Diagram
FBD Block
| Operand | Data Type | Format | Description | 
|---|---|---|---|
| MUL | FBD_MATH | tag | MUL structure | 
FBD_MATH Structure
| Input Members | Data Type | Description | 
|---|---|---|
| EnableIn | BOOL | Enable input. If false, the instruction does not execute and outputs are not updated.
                   Default is true. | 
| SourceA | REAL | Value of the multiplicand. | 
| SourceB | REAL | Value of the multiplier. | 
| Output Members | Data Type | Description | 
|---|---|---|
| EnableOut | BOOL | Indicates if the instruction executed without fault when it was enabled. | 
| Dest | REAL | Result of the instruction. | 
FBD Function
     TIP: 
    
 FBD Function is applicable to CompactLogix 5380, CompactLogix 5480, ControlLogix 5580, Compact GuardLogix 5380, and GuardLogix 5580 controllers only.
| Input Operands (Left Pins) | CompactLogix 5380, CompactLogix 5480, ControlLogix 5580, Compact GuardLogix 5380, and GuardLogix 5580 controllers Data Type | Description | 
|---|---|---|
| SourceA (top) | SINT USINT INT UINT DINT UDINT LINT ULINT REAL LREAL  | Value of the multiplicand. | 
| SourceB (bottom) | SINT USINT INT UINT DINT UDINT LINT ULINT REAL LREAL  | Value of the multiplier. | 
| Output Operand (Right Pin) | CompactLogix 5380, CompactLogix 5480, ControlLogix 5580, Compact GuardLogix 5380, and GuardLogix 5580 controllers Data Type | Description | 
|---|---|---|
| Dest | DINT UDINT LINT ULINT REAL LREAL  | Result of the function. | 
See 
FBD Functions
.Affects Math Status Flags
| Controllers | Affects Math Status Flag | 
|---|---|
| CompactLogix 5380, CompactLogix 5480, ControlLogix 5580, Compact GuardLogix 5380, and GuardLogix 5580 controllers | Conditional | 
| CompactLogix 5370, ControlLogix 5570, Compact GuardLogix 5370, and GuardLogix 5570 controllers | Yes | 
See Math Status Flags.
Major/Minor Faults
None specific to this instruction. See Index Through Arrays for array-indexing faults.
Execution
Ladder Diagram
| Condition/State | Action Taken | 
|---|---|
| Prescan | N/A | 
| Rung-condition-in is false | Set Rung-condition-out to Rung-condition-in | 
| Rung-condition-in is true | Set Rung-condition-out to Rung-condition-in Dest = Source A x Source B | 
| Postscan | N/A | 
Function Block Diagram
| Condition/State | Action Taken | 
|---|---|
| Prescan | N/A | 
| EnableIn is false | Set EnableOut to EnableIn | 
| EnableIn is true | Dest = SourceA x SourceB If overflow occurs  Clear EnableOut to false else  Set EnableOut to true | 
| Instruction first run | N/A | 
| Instruction first scan | N/A | 
| Postscan | N/A | 
FBD Function
     TIP: 
    
 FBD Function is applicable to CompactLogix 5380, CompactLogix 5480, ControlLogix 5580, Compact GuardLogix 5380, and GuardLogix 5580 controllers only.
| Condition/State | Action Taken | 
|---|---|
| Prescan | N/A | 
| Normal Scan | Dest = Source A x Source B | 
| Instruction first run | N/A | 
| Instruction first scan | N/A | 
| Postscan | N/A | 
Examples
Ladder Diagram

Function Block Diagram
FBD Block

FBD Function

Structured Text
REAL_dest := REAL_srcA * REAL_srcB;