Push Agent properties

Configure Push Agent properties to send data to the cloud using MQTT.
Property name
Property type
Property description
DataLogger
NodeId
A reference to the data logger instance.
DataLoggerPullTme
Duration
The time interval after which data is taken from the data logger and stored in the auxiliary store. If
PreserveDataLoggerHistory
is set to
True
, the original data is deleted from the data logger after copying it to the auxiliary store.
PushFullSample
Boolean
If
True
, the
by line
transfer mode is used.
If
False
, the
by variable
transfer mode is used.
PreserveDataLoggerHistory
Boolean
If
True
, the data is sent and historicized.
If
False
, every time the data is transferred to the auxiliary store, the data is deleted from the data logger.
MaximumStoreCapacity
Int32
The maximum capacity of the auxiliary store used by the Push Agent.
MaximumItemsPerPacket
Int32
The number of records encapsulated in a packet.
by line
transfer mode sends only one line per packet.
TIP: When
PushFullSample
is set to
True
, set the
MaximumItemsPerPacket
to
1
.
MaximumPublishTime
Duration
The maximum time interval after which data is taken from the auxiliary store and sent to the cloud. The interval is used when the auxiliary store has fewer records than
MaximumItemsPerPacket
.
MinimumPublishTime
Duration
The minimum time interval after which data is taken from the auxiliary store and sent to the cloud. The interval is used when the auxiliary store has more records than
MaximumItemsPerPacket
. You may want to increase the sending frequency to download the queue of the store.
ClientId
String
The
ID
of the client that has to send the data.
BrokerIPAddress
String
The broker IP address or hostname.
BrokerPort
Int32
The broker port (if you want to communicate with SSL, set the value to
8883
).
BrokerTopic
String
The name of the topic you want to publish on preceded by
/
.
QoS
Int32
The Quality Of Service (QoS) level used to send information.
0
AT_MOST_ONCE
1
AT_LEAST_ONCE
2
EXACTLY_ONCE
UseSSL
Boolean
Enables or disables secure communication.
CACert
The path to the file that contains the CA (must be in the
PEM
format).
ClientCert
The path to the file that contains the client certificate (must be in the
PFX
format).
ClientCertPassword
The password of the client certificate.
IMPORTANT: Use the newest OpenSSL library and encryption algorithm supported in .NET to generate the PFX certificates. If you use the RC2 algorithm to generate the PFX certificate, certificate-based authentication for Azure IoT Hub fails on the terminal
Username
String
The username for authenticated communication with the broker.
Password
Password
The password for authenticated communication with the broker.