5034-SERIAL and 5034-SERIALXT Serial RS-232/RS-422/RS-485 1 Channel Module

5034-SERIAL and 5034-SERIALXT Wiring Diagram – RS-232 Mode DTE Device
5034-SERIAL and 5034-SERIALXT Wiring Diagram – RS-232 Mode DCE Device
5034-SERIAL and 5034-SERIALXT Wiring Diagram – RS-485 Mode
IMPORTANT:
  • Place the termination resistor between TRXD+ and TRXD- to implement this wiring.
  • The recommended cable to use is Belden 8104.
5034-SERIAL and 5034-SERIALXT Wiring Diagram – RS-422 Mode
IMPORTANT:
  • Place the termination resistor between RXD+ and RXD- to implement this wiring.
  • The recommended cable to use is Belden 8104.
5034-SERIAL and 5034-SERIALXT Functional Block Diagram
Technical Specifications - 5034-SERIAL, 5034-SERIALXT
Attribute
5034-SERIAL, 5034-SERIALXT
Operating modes
Generic ASCII
Modbus RTU
Modbus ASCII
Serial input signal voltage range
+3…+25V DC regarding signal ground (SG) 0, Asserted, ON, Space, Active
-3…-25V DC regarding signal ground (SG) 1, Deasserted, OFF, Mark, Inactive
Handshaking
RTS/CTS hardware handshake always enabled
RTS/CTS user-controllable
Supported communication rate (bps)
1200, 2400, 4800, 9600, 19200 (Default), 38400, 57600, 115200
General Specifications - 5034-SERIAL, 5034-SERIALXT
Attribute
5034-SERIAL, 5034-SERIALXT
Number of inputs
One full-duplex (RS-232, RS-422)/half-duplex (RS-485)
Voltage category
24V DC source
SA power voltage, nom
24V DC
SA power voltage range
10…30V DC
SA power current, nom
20 mA
SA power current, max
30 mA
SA power current at no load
15 mA
SA reverse polarity protection
Yes
Power dissipation, max
(1)
0.35 W
Thermal dissipation, max
(1)
1.20 BTU/hr
Isolation voltage
250V (continuous), Basic Insulation Type, System to SA power
250V (continuous), Basic Insulation Type, SA power to Communication channel
250V (continuous), Basic Insulation Type, System to Communication channel
RIUP support
Yes
Electronic keying
Electronic keying via programming software
RTB key positions (slot)
3, 5, 11
RTB supported
5034-RTB18, 5034-RTB18S
Wiring category
(2)
2 - Signal ports
2 - Power ports
Wiring specification
See Wiring Specifications for Removable Terminal Blocks in the PointMax I/O System Specifications Technical Data, publication 5034-TD001
Indicators
1 green/red module status indicator
1 green/red SA power status indicator
2 yellow/red I/O status indicators
Dimensions (HxWxD), approx
123.6 x 15.0 x 66.4 mm (4.87 x 0.59 x 2.61 in.)
Weight, approx
45.0 g (1.59 oz.) – 5034-SERIAL
47.0 g (1.66 oz.) – 5034-SERIALXT
Enclosure type
None (Open-style)
North American temp code
T4
UKEX/ATEX temp code
T4
IECEx temp code
T4
(1) Value is measured at 60 °C (140 °F). Power dissipation varies with temperature.
(2) Use this Conductor Category information for planning conductor routing. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1. Use this Conductor Category information for planning conductor routing as described in the appropriate System Level Installation Manual.